9R143 Dated 3/2011
i
Meriam’s M2110L Smart Level Gauge is
a microprocessor-based pressure sensing
device with algorithms to calculate level.
The various sensors provide dip- tube
bubbler accommodation, or direct head
level measurements. Three config-
urations are available: Battery, SetPoint,
and Current Loop models.
All models are programmable through the
front keypad, to allow configuration of
the gauge. The user’s program
information is stored in non-volatile
memory, and is retained when the power
to the gauge is removed. SetPoint and
Current Loop models can also be
configured through the RS-232 serial
communication connection.
The Battery model is powered by its internal lithium batteries only. This model does not provide
any outputs or RS-232 communications.
SetPoint and Current Loop models have outputs that can be used for control or
indicating/recording functions. Both models also have RS-232 communications capability. In
addition to configuring the gauge, the RS-232 port can be used to monitor and log the measured
level/pressure data and output status. It can also be used as part of a control system with digital
capabilities.
The SetPoint model provides two SPDT relay outputs with adjustable deadband. This
configuration provides normally open or normally closed contact operation for fail-safety.
Switching SetPoint can be set from 0 to +120% of the full scale level/pressure range. The
SetPoint model is powered by 115/230 VAC, or 24VDC.
The Current Loop model provides a 4 to 20 mA output, and is intended to be used as a level
transmitter on a three or four wire loop. Zero and span are set through user-programmable
registers, from 0 to +120% of the full scale pressure range. The output is capable of normal and
reverse action. The Current Loop model is powered by 24VDC only.
M2110L SMART LEVEL GAUGE
OPERATING INSTRUCTIONS
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - OPERATING INSTRUCTIONS

9R143 Dated 3/2011 i Meriam’s M2110L Smart Level Gauge is a microprocessor-based pressure sensing device with algorithms to calculate level.

Page 2 - Table of Contents

9R143 Dated 3/2011 8 ZERO REFERENCE Zeroing the gauge consists of accepting the current applied pressure value as the zero pressure reference. To

Page 3 - LEVEL DISPLAY

9R143 Dated 3/2011 9 P0 – LOCKOUT CODE This feature provides security in the Smart Gauge. It is designed to prevent unauthorized personnel from ta

Page 4 - SAFETY WARNINGS

9R143 Dated 3/2011 10 P1 – TIMEOUT VALUE This register sets the length of time (in minutes) for automatic shutoff. The Battery model will automati

Page 5

9R143 Dated 3/2011 11 P2 – DAMP RATE The Smart Gauge has a selectable damp rate, which is used to stabilize the display for applications with a pul

Page 6 - KEYPAD FUNCTIONS:

9R143 Dated 3/2011 12 P3 – RESIDUAL HYDROSTATIC PRESSURE The M2110L Smart Level Gauge will correctly measure level when used with a dip tube or as

Page 7

9R143 Dated 3/2011 13 Press the Up↑ or Down↓ keys repeatedly to scroll to the desired register. 3 The Zero function (Up↑ and Down↓) will reset the

Page 8

9R143 Dated 3/2011 14 P4 – FULL TANK HYDROSTATIC PRESSURE This register is used by the gauge to draw a relationship between measured static pressur

Page 9 - ENGINEERING UNITS

9R143 Dated 3/2011 15 P5 – SETPOINT OPTIONS This register defines the output action for SetPoint and Current Loop models. Note that if an output i

Page 10 - ZERO REFERENCE

9R143 Dated 3/2011 16 P6 and P7 – SETPOINT (SET1 and SET2) SetPoint Model These registers define the pressure points at which the SPDT relays wi

Page 11 - P0 – LOCKOUT CODE

9R143 Dated 3/2011 17 P8 – DEADBAND This register is found on the SetPoint model only. It sets the adjustable deadband for the SPDT relays. Deadb

Page 12 - P1 – TIMEOUT VALUE

9R143 Dated 3/2011 ii Table of Contents LEVEL DISPLAY...

Page 13 - P2 – DAMP RATE

9R143 Dated 3/2011 18 P9 – TANK CYLINDRICAL CAPACITY The Smart Level Gauge calculates level based on measured hydrostatic pressure, by drawing a re

Page 14

9R143 Dated 3/2011 19 P10 – TANK ENDS CAPACITY The Smart Level Gauge calculates level based on measured hydrostatic pressure, by drawing a relation

Page 15

9R143 Dated 3/2011 20 P11 – TANK TYPE This register identifies the type of tank application, with respect to the vertical fluid pressure measureme

Page 16

9R143 Dated 3/2011 21 LOCKOUT CODE PROMPT DESCRIPTION When a gauge is “locked” for security purposes, it does not allow access to change its oper

Page 17 - P5 – SETPOINT OPTIONS

9R143 Dated 3/2011 22 SERIAL PORT SERVICE The M2110L Smart Level Gauge SetPoint models and Current Loop models provide RS-232C communication capab

Page 18

9R143 Dated 3/2011 23 IMPACT ON OPERATION Use of the serial port service is independent of the operating mode of the gauge, and vice versa. It i

Page 19 - P8 – DEADBAND

9R143 Dated 3/2011 24 ERROR CODES All Smart Gauge models have an error/message feature to inform the operator of problems with the operation or pr

Page 20

9R143 Dated 3/2011 25 INSTALLATION AND WIRING The SetPoint model utilizes the multi-function terminal strip shown at the left. This

Page 21 - P10 – TANK ENDS CAPACITY

9R143 Dated 3/2011 26 CURRENT LOOP MODEL LOOP WIRING Note: R = Receiving Device 24 VDC/ 50 mA

Page 22 - P11 – TANK TYPE

9R143 Dated 3/2011 27 OUTLINE DIMENSIONS PANEL MOUNTING 1. Make a ¼ DIN panel cutout per drawing. 2. Remove the two 6-32 socket head sc

Page 23 - LOCKOUT CODE PROMPT

9R143 Dated 3/2011 1 LEVEL DISPLAY Indicators During normal operation, the gauge displays the level value in large numerals, and the bottom of t

Page 24 - SERIAL PORT SERVICE

9R143 Dated 3/2011 28 PRODUCT SPECIFICATIONS TYPE & RANGE: DN: Differential Non-isolated DI Differential Isolated GI: Gauge Isolated

Page 25

9R143 Dated 3/2011 29 RANGE LIMITS AND INDICATION Sensor Hard Soft Certified Soft Hard Type Under Under Range Over Over Range Ran

Page 26 - ERROR CODES

9R143 Dated 3/2011 30 SERVICE AND CALIBRATION In the event an M2110 requires service or needs to be returned for factory recertification, battery

Page 27 - INSTALLATION AND WIRING

9R143 Dated 3/2011 2 SAFETY WARNINGS The table below defines the safety symbols, signal words and corresponding safety messages used in the manual

Page 28

9R143 Dated 3/2011 3 CERTIFICATION / SAFETY / WARNINGS Fire/Explosion Hazard. This instrument is not intrinsically safe. DO NOT use or service in

Page 29

9R143 Dated 3/2011 4 KEYPAD FUNCTIONS: The keys on the front panel perform multiple functions. Their function differs depending on whether the gau

Page 30 - Sensor Ranges

9R143 Dated 3/2011 5 PRGM/Enter Key PRGM Document Symbol: (PRGM/Enter→) Measure Mode (and EU Selection) Selects Program Mode, which allows acce

Page 31 - RANGE LIMITS AND INDICATION

9R143 Dated 3/2011 6 PROGRAMMABLE REGISTER OVERVIEW All M2110L Smart Level Gauges have programmable registers that allow the gauge to be configure

Page 32 - SERVICE AND CALIBRATION

9R143 Dated 3/2011 7 ENGINEERING UNITS The following Engineering Units are available on the M2110L Smart Level Gauge: 1. Gallons 2. Pounds 3.